What needs to be clarified
Recalculate by actual sections and operating modes, assessing route length, conductor material and circuit topology.
Materials to prepare
- Calculation file with formulas and units
- As-built route, sections, conductor sizes and materials
- Load data and available operating-voltage records
What to compare
Reconstruct sections, verify length units and single/three-phase formulas. Check resistance, power factor and current assumptions. Recalculate steady operation and starting separately; compare available readings at both ends under matching load conditions.
Possible outcome of the analysis
A section table may show influential assumptions, sensitivity to unknowns and the additional measurements required for this particular circuit.
Limits of the conclusions
Voltage-drop calculation does not check protection or cable heating. Unknown route and starting parameters limit the corresponding estimate.